emerLED
Emergency lighting kits with self-diagnosis function for constant current LED luminaires.Ref. No. | Operating voltages under normalVconditionsdefective | Battery included | Nominal perfomanceh | Operating temp.ta (ºC) | Set weighKg | Código batería | Battery weightKg | Holder code | Holder weightKg | ||
---|---|---|---|---|---|---|---|---|---|---|---|
emerLED 12-50V 3W 1h | 9953061 | 12...50 | -...60V | 4,8V 1,8 Ah NiCd | 1 | +5…+50 | 0,343 | 9513041 | 0,2 | 9331700 | 0,004 |
emerLED 12-50V 3W 3h | 9953062 | 12...50 | -...60V | 4,8V 4,5 Ah NiCd | 3 | +5…+50 | 0,66 | 9513051 | 0,5 | 9331701 | 0,011 |
emerLED 30-220V 3W 1h | 9953063 | 30...220 | -...250V | 4,8V 1,8 Ah NiCd | 1 | +5…+50 | 0,343 | 9513041 | 0,2 | 9331700 | 0,004 |
emerLED 30-220V 3W 3h | 9953064 | 30...220 | -...250V | 4,8V 4,5 Ah NiCd | 3 | +5…+50 | 0,661 | 9513051 | 0,5 | 9331701 | 0,011 |
The emerLED has to be used in combination with a constant current control gear for LED modules in LED luminaires.
Electrical protection: Class I.
Protection rating: IP 20.
Automatic test according EN 62034.
Valid for DIN 0108 / EN 50172 installations.
Suitable for cables 0,5-1,5 mm2 section stripping 8 mm.
The battery holders must be ordered separately.
Polyvalent emergency lighting unit. Suitable for every configuration.
The maximum operating current in the LED module has to be lower than 2,5A.
In case of mains failure, emerLED units have an additional fifth pole to disconnect the mains. So the LED module is completely isolated from the driver; ensuring its correct re-ignition when it returns to normal operating mode.
Batteries are supplied discharged.
For a functional test a 10 minutes charge period should be enough.
To obtain full performance it has to be connected to the mains at least 48 hours.
These emerLED modules include an automatic self-diagnostic at regular intervals. Every 8 days the correct performance of the module, the light and the battery is tested.
Every 12 weeks the capacity of the batteries is tested simulating a mains failure and making a performance test.
That is the reason why there’s only need for a visual and periodical inspection LED display and the installation.
Permitted input voltage AC: 207-253V.